AWG
18 (Solid) Bare Copper |
|
Aero
P/N |
#
of Pair |
Insulation
Thickness (inches) |
Jacket
Thickness (inches) |
Jacket
O.D. (inches) |
Lbs
/ 1000' |
Shielded |
7140K |
1 |
.016 |
.025 |
.206 |
34 |
7240K |
2 |
.016 |
.025 |
.320 |
58 |
Unshielded |
7141K |
1 |
.016 |
.025 |
.202 |
28 |
7241K |
2 |
.016 |
.025 |
.316 |
52 |
|
|
|
|
|
|
AWG
16 (Solid) Bare Copper |
|
Aero
P/N |
#
of Pair |
Insulation
Thickness (inches) |
Jacket
Thickness (inches) |
Jacket
O.D. (inches) |
Lbs
/ 1000' |
Shielded |
7130K |
1 |
.016 |
.025 |
.228 |
45 |
7230K |
2 |
.016 |
.025 |
.358 |
77 |
7330K |
3 |
.016 |
.025 |
.381 |
102 |
Unshielded |
7131K |
1 |
.016 |
.025 |
.224 |
37 |
7231K |
2 |
.016 |
.025 |
.354 |
69 |
7331K |
3 |
.016 |
.025 |
.377 |
93 |
|
|
|
|
|
|
AWG
14 (Solid) Bare Copper |
|
Aero
P/N |
#
of Pair |
Insulation
Thickness (inches) |
Jacket
Thickness (inches) |
Jacket
O.D. (inches) |
Lbs
/ 1000' |
Shielded |
7120K |
1 |
.016 |
.025 |
.254 |
62 |
7220K |
2 |
.016 |
.025 |
.404 |
106 |
Unshielded |
7121K |
1 |
.016 |
.025 |
.250 |
49 |
7221K |
2 |
.016 |
.025 |
.400 |
93 |
|
|
|
|
|
|
AWG
12 (Solid) Bare Copper |
|
Aero
P/N |
#
of Pair |
Insulation
Thickness (inches) |
Jacket
Thickness (inches) |
Jacket
O.D. (inches) |
Lbs
/ 1000' |
Shielded |
7110K |
1 |
.016 |
.025 |
.288 |
88 |
7210K |
2 |
.016 |
.025 |
.463 |
151 |
Unshielded |
7111K |
1 |
.016 |
.025 |
.284 |
68 |
7211K |
2 |
.016 |
.025 |
.459 |
131 |
|
|
|
|
|
|
|
|
Specifications |
|
Conductor:
Solid BC
Insulation:
FEP
Color Code:
Chart 3
Except 2/P (Blk/Red, Wht/Grn)
Jacket:
E-CTFE (150°C)
Industry Approvals:
(UL) FPLP also classified
NYC Cert Fire Alarm Cable
Impedance: (Ohms Nom.)
|
Unshielded |
Shielded |
(AWG 18) |
117 |
64 |
(AWG 16) |
103 |
56 |
(AWG 14) |
92 |
49 |
(AWG 12) |
82 |
43 |
|
Vel. of Propagation:
69% Nom.
Capacitance: (pF/FT Nom.)
|
Unshielded |
Shielded |
(AWG 18) |
13 |
23 |
(AWG 16) |
14 |
27 |
(AWG 14) |
16 |
30 |
(AWG 12) |
18 |
35 |
Temperature Rating:
-40°C to +150°C (FEP/E-CTFE)
Put Ups:
1000 feet (+/- 10%)
(Available in Bulk Reels) |