AWG
16 (7x24) Tinned Copper
|
Aero
P/N |
#
of Cond. |
Insulation
Thickness (inches) |
Jacket
Thickness (inches) |
Jacket
O.D. (inches) |
Lbs
/ 1000' |
1236/7 |
2 |
.010 |
.010 |
.178 |
31 |
1336/7 |
3 |
.010 |
.010 |
.190 |
41 |
1436/7 |
4 |
.010 |
.010 |
.210 |
52 |
1636/7 |
6 |
.010 |
.012 |
.259 |
76 |
1736/7 |
7 |
.010 |
.012 |
.259 |
87 |
1936/7 |
9 |
.010 |
.015 |
.342 |
113 |
1136/7 |
12 |
.010 |
.015 |
.354 |
145 |
|
|
|
|
|
|
AWG
14 (19x.0147") Tinned Copper |
|
Aero
P/N |
#
of Cond. |
Insulation
Thickness (inches) |
Jacket
Thickness (inches) |
Jacket
O.D. (inches) |
Lbs
/ 1000' |
1226 |
2 |
.012 |
.015 |
.216 |
49 |
1326 |
3 |
.012 |
.015 |
.230 |
63 |
1426 |
4 |
.012 |
.015 |
.253 |
79 |
1626 |
6 |
.012 |
.015 |
.307 |
109 |
1726 |
7 |
.012 |
.015 |
.307 |
124 |
1926 |
9 |
.012 |
.015 |
.398 |
156 |
1126 |
12 |
.012 |
.015 |
.412 |
199 |
|
|
|
|
|
|
AWG
12 (19x.0185") Tinned Copper |
|
Aero
P/N |
#
of Cond. |
Insulation
Thickness (inches) |
Jacket
Thickness (inches) |
Jacket
O.D. (inches) |
Lbs
/ 1000' |
1216 |
2 |
.012 |
.015 |
.250 |
71 |
1316 |
3 |
.012 |
.015 |
.266 |
93 |
1416 |
4 |
.012 |
.015 |
.294 |
116 |
1616 |
6 |
.012 |
.015 |
.358 |
162 |
1716 |
7 |
.012 |
.015 |
.358 |
183 |
1916 |
9 |
.012 |
.015 |
.466 |
231 |
1116 |
12 |
.012 |
.015 |
.482 |
296 |
|
|
|
|
|
|
AWG
10 (37x26) Tinned Copper |
|
Aero
P/N |
#
of Cond. |
Insulation
Thickness (inches) |
Jacket
Thickness (inches) |
Jacket
O.D. (inches) |
Lbs
/ 1000' |
1206 |
2 |
.012 |
.015 |
.302 |
105 |
1306 |
3 |
.012 |
.015 |
.322 |
139 |
1406 |
4 |
.012 |
.015 |
.357 |
172 |
1606 |
6 |
.012 |
.015 |
.436 |
241 |
1706 |
7 |
.012 |
.015 |
.436 |
273 |
1906 |
9 |
.012 |
.015 |
.570 |
344 |
1106 |
12 |
.012 |
.015 |
.590 |
442 |
|
|
|
|
|
|
|
|
Specifications |
|
Conductor:
Stranded TC
Insulation:
FEP (200°C)
Color Code:
Chart 1
Shield:
Aluminum/Mylar and Drain
Jacket:
FEP (200°C)
Impedance:
(AWG 16) 45 Ohms Nom.
(AWG 14) 43 Ohms Nom.
(AWG 12) 39 Ohms Nom.
(AWG 10) 33 Ohms Nom.
Vel. of Propagation:
69% Nom.
|
Capacitance:
(AWG 16) 32 pF/FT Nom.
(AWG 14) 34 pF/FT Nom.
(AWG 12) 38 pF/FT Nom.
(AWG 10) 45 pF/FT Nom.
Voltage:
Spark tested @ 5 KV for use as 600 Volts Control
Temperature Rating:
-80°C to +200°C
(Insulation & Jacket only)
Put Ups:
1000 Feet (+/- 10%)
(Available in Bulk Reels) |